topleft
topright
 
Option H - HART CP-10/CP-11Popular

Features:

The Hart option board provides a Bell 202 interface to devices supporting the Hart protocol.

Each Hart option board can be used to communicate with up to 15 Hart devices. When communicating with a single Hart device (point to point installation), both analog and digital data can be read. When communicating with multiple Hart devices (multidrop installation) only digital data can be read.

 

Up to two Hart option boards can be installed on the one RTU allowing up to 2 point to point circuits or 2 multidrop circuits.

If using two separate point to point circuits and reading analog data, the RTU analog input channels must be isolated from each other.

 
  • HART Protocol option board
  • Communicates with up to 15 HART devices
  • Fits CP-10, CP-11, CP-21, MC-11
  • COMMS-OPTION-H (Hart Interface (Limited functionality-refer to Product specifications) for CP-11/CP-21/MC-11, option port 2/3)
  • Product specifications

    General
       
    Baudrate
    1200 Baud, ˝ Duplex
    Modulation Bell 202
    Logical Frequencies 1 = 1200 Hz
    0 = 2200 Hz
    Configuration Software Toolbox
    Internal Power Consumption 1 mA from +5VDC Bus on backplane
    Maximum No. Hart Devices 15 (multidrop)
    Data Available Digital and analog for point to point
    Digital only for multidrop
       
    Environmental
       
    Operating Temperature -20°C to 70°C / -4°F to 158°F
    Storage Temperature -40°C to 85°C / -40°F to 185°F
    Operating Humidity 5 to 98% RH non-condensing

    Print Datasheet


    Last updated: 2006-09-26 21:12:17
    © 2008 RTUnet. All rights reserved. Information subject to change without notice.